TPI 712 Deluxe Combustion Analyzer with Optional PC Interface. All the features of the 709R PLUS checks combustibles in flue, optional PC interface.
Features
QUICK AND SIMPLE SET UP - All TPI analyzers feature quick and simple set up. Fast purge and the ability to perform fuel selection during start up enable tests to be
performed quickly without requiring extra set-up time after initial startup.
TPI analyzers also use the last selected fuel as the default setting. This feature prevents the need to perform fuel selection every time the analyzer is turned on.
- Calculates combustion efficiency
- Pump driven for fast response
- Built-in differential manometer with 0.001” H2O resolution
- Will not shut off if 15 ppm CO is present for increased safety
- Ten selectable fuels
- Optional A740 IR printer available for hard copies of test results
- Communicate to a PC via the optional A767 IR interface
- Built-in differential thermometer
- Data Logging with time and date stamp
- Store function to save up to 50 readings
- Push on fittings for fast and easy use
- Large easy to read backlit display
Specifications
- Operating Temperature Range: 14°F to +122°F (-10°C to +50°C)
- Battery/Batery Life Rechargeable Ni-MH / > 6 Hours
- Charger Input Voltage 115V or 230V : 50/60 Hz AC
- Fuels: Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse
- Units of Pressure mbar, kPa & inH2O
- Display: 3 Line Backlit LCD w/annunciators
- Data Storage: 10 sets of readings
- Data Logging: 400 sets of readings
- Single Logging: 150 sets of readings
- Time & Date: 24 Hour Real Time Clock
Gas/Range/Resolution/Accuracy
- Oxygen: 0-25%, 0.1%, +/- 0.3%
- Carbon Monoxide: 0-10,000 ppm, 1 ppm, +/- 5 ppm or 5%
- Carbon Dioxide: 0-25%, 0.1%, Calculated
- CO/CO2 Ratio: 0-0.999, 0.001, Calculated
- Combustion Eff.: 0-100%, 0.1%, Calculated
- Gas Leak Sensor: 100-10,000 ppm
Temperature Measurement
- Input Type: K-Type thermocouple
- Range: -58°F to 1832°F (-50°C to 1000°C)
- Resolution: 1°F (1°C)
- Accuracy: +/- (0.3% of rdg + 2°F) or +/- (0.3% of rdg + 1°C)
Pressure Measurement
- Selectable Ranges mbar, kPa and inH2O
- Range -120 inH2O to 120 inH2O
- Resolution 0.001 inH2O
- Accuracy +/- 0.5% fsd
Standard accessories
- Flue Probe with K-Type #A770
- K-Type Temperature Probe #GK11M
- In-Line Filter Complete #A762
- Mini Pump Protection Filter Assembly #A763
- Carrying Case #A768
- Protective Rubber Boot A765